Objects Analog values Read/Write Availability of analog value objects
FMS2M-Bx1x FMS2M-Bx2x FMS2M-Bx3x FMS2M-Bx4x
AV-13 NV Temperature 3 Read or write No No Yes Yes
AV-14 Low alarm setpoint 3 Read or write No No Yes Yes
AV-15 Low warning setpoint 3 Read or write No No Yes Yes
AV-16 High warning setpoint 3 Read or write No No Yes Yes
AV-17 High alarm setpoint 3 Read or write No No Yes Yes
AV-18 NV Humidity 3 Read or write No No Yes Yes
AV-19 NV Temperature 4 Read or write No No No Yes
AV-20 Low alarm setpoint 4 Read or write No No No Yes
AV-21 Low warning setpoint 4 Read or write No No No Yes
AV-22 High warning setpoint 4 Read or write No No No Yes
AV-23 High alarm setpoint 4 Read or write No No No Yes
AV-24 NV Humidity 4 Read or write No No No Yes
Objects Multistate objects Read/Write Availability of multistate objects
FMS2M-Bx1x FMS2M-Bx2x FMS2M-Bx3x FMS2M-Bx4x
MV-1 Isolation mode:
1 = positive, 2 = negative, 3 = neutral
Read only Yes Yes Yes Yes
MV-2 Status 1:
1 = normal, 2 = warning, 3 = alarm
Read only Yes Yes Yes Yes
MV-3 Status 2:
1 = normal, 2 = warning, 3 = alarm
Read only No Yes Yes Yes
MV-4 Status 3:
1 = normal, 2 = warning, 3 = alarm
Read only No No Yes Yes
MV-5 Status 4:
1 = normal, 2 = warning, 3 = alarm
Read only No No No Yes
Table 21: Multistate objects for integration in a BMS