Maximum operating pressure 125 PSI (862 kPa)
Minimum operating pressure 4 PSI (27.5 kPa)
Maximum ambient air temperature 122
0
F (50
0
C)
Minimum ambient air temperature 32
0
F (0
0
C)
Maximum humidity 100%
Maximum hardness 120 ppm
(7 grains per gallon)
Maximum iron 0.3 ppm
Minimum UVT 75%
Installation Vertical or horizontal*
Rated service life of lamp 1 year
Certification**
Maximum rated
flow at dose of
16 mJ/cm
2
3 GPM
(11 LPM)
6 GPM
(23 LPM)
16 GPM
(60 LPM)
16 GPM
(60 LPM)
29 GPM
(110 LPM)
45 GPM
(170 LPM)
Maximum rated
flow at dose of
30 mJ/cm
2
1 GPM
(4 LPM)
4 GPM
(15 LPM)
9 GPM
(34 LPM)
9 GPM
(34 LPM)
15 GPM
(57 LPM)
25 GPM
(95 LPM)
Maximum rated
flow at dose of
40 mJ/cm
2
1 GPM
(4 LPM)
3 GPM
(11 LPM)
7 GPM
(26 LPM)
7 GPM
(26 LPM)
12 GPM
(45 LPM)
20 GPM
(76 LPM)
Voltage 120V or 230V AC 100-240V AC 100-240V AC 100-240V AC 100-240V AC 100-240V AC
Frequency 50-60 Hz 50-60 Hz 50-60 Hz 50-60 Hz 50-60 Hz 50-60 Hz
Max. current 0.4 Amp 0.4 Amp 0.5 Amp 0.5 Amp 0.85 Amp 1.2 Amp
Max. power
consumption
22 Watts 36 Watts 50 Watts 50 Watts 83 Watts 130 Watts
Lamp power 14 Watts 25 Watts 40 Watts 40 Watts 70 Watts 110 Watts
UV Chamber
Material
304 SST 304 SST 304 SST 304 SST 316 SST 316 SST
Inlet/Outlet 3/8" FNPT 3/4" NPT 3/4" NPT 3/4" NPT 1" NPT 1" NPT
Flow rates shown are at 85% UVT.
*Systems with sensors must be installed vertically.
**Model A is only system certified by CSA and not by UL.