EasyManuals Logo

Trox VFC series User Manual

Default Icon
12 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
6
Operating manual
TROX air terminal units
Type VFC volume ow controllers
Actuator E01 ... E03
Setting the set ow rate
Each VFC carries a characteristic to determine the setting
values on site (see example, nominal size 160).
min
values below 3 results in an unregulated airow dependent
on the duct pressure that is not less than
min-unit
.
Set the set ow rate as follows:
Determine the setting value for the set ow rate from the
characteristic or the table on page 5.
Set the values on the
min
- and
max
potentiometers.
Factory setting:
min
= 4
max
= 8
Shut-o down to leakage airow is possible, value to be set 0
Functional test
A functional test can be performed very easily using the service
button and the indicator light.
Press service button for at least 1 second
Actuator turns toward 
min
Actuator turns toward 
max
Actuator returns to control mode
Indicator light provides functional information
Permanently on : Position set
Flashing once a second : Actuator operating
Flashing twice a second : Actuator is jammed and stationary
O : No supply voltage
Actuator E03
The relationships between the setting value and output signal
U, or control signal w, are shown in the two characteristics on
the left.
The output signal does not correspond to the currently
measured volume flow rate, but reflects the setpoint value.
Example:
Factory set values:
min
= 4
min
= 8
Required value: 6
--> Required control signal: 5 V
Available output signal: 6 V corresponding to set value 6
max
potentiometer
Indicator light
Service button
min
potentiometer
Variable volume ow rate operation, actuator with
potentiometers
Characteristic for determining the volume ow rate
0
6
10
0
6 V
10 VDC
0
6
4
8
10
max
min
05 V 10 VDC
Characteristic of the actual value signal
Characteristics of the control signal
Output signal U
Control signal w
Value to be set
Value to be set
E03
E03
60 100
65
5038 100 150 200 250 300 350 392
VFC 160
18 40 80 120 140
185
160 180
100
200 300 400 500 550450350250150 666600 650
3
4
5
6
7
8
9
10
l/s
cfm
m³/h

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trox VFC series and is the answer not in the manual?

Trox VFC series Specifications

General IconGeneral
BrandTrox
ModelVFC series
CategoryController
LanguageEnglish