18 Part Two
CONFIGURE MENU
MENU ITEM
Monitor/
Controller
SOFTWARE
NAME
ITEM DESCRIPTION
ITEM RANGE
DEFAULT
VALUE
NORMAL
CONTROL MODE
FHC50 Only
NORM CTRL
MODE
The NORM CTRL MODE item selects the measurement on
which the control function is based during NORMAL (Occupied)
Mode.
If this item is set to:
VelSidewall The controller will control face velocity using a
sidewall sensor.
VelSashPos The controller will control face velocity using a
sash sensor and venturi valve with LOM
feedback.
VelSide+Sash The controller will control face velocity using
both the sash sensor with LOM feedback and a
sidewall sensor.
Flow The controller will control flow using the flow
device (see menu item FLOW DEVICE).
VelSidewall
VelSashPos
VelSide+Sash
Flow
VelSideWall