The SETB CTRL MODE item selects the measurement on
which the control function is based during SETBACK
(Unoccupied) Mode.
If this item is set to:
VelSidewall The controller will control face velocity using a
sidewall sensor.
VelSashPos The controller will control face velocity using a
sash sensor and venturi valve with LOM
feedback.
VelSide+Sash The controller will control face velocity using
both the sash sensor with LOM feedback and a
sidewall sensor.
Flow The controller will control flow using the flow
device (see menu item FLOW DEVICE).
FixedPos The controller will hold the damper or venturi
valve at a fixed percentage at all times during
SETBACK Mode, while ignoring the measured
face velocity or flow for control purposes. All
SETBACK-related alarms are still active with
this configuration, unless set to OFF.
NOTE: To shutdown a fume hood with the Model FHC50
controller, set the SETB CTRL MODE item to
FixedPos and the SETBACK POS item to 0%.
The VEL SENSOR item shows if the velocity sensor input is
enabled. If this item shows Enabled, then the controller will look
for and use an installed sidewall sensor. If this item shows
Disabled, the controller will not look for or use an installed
sidewall sensor.