2. STANDBY MODE
The Configuration Menu - accessible via the letter [M] - is used to set the parameters of the digital unit.
To access it, you must enter your secret code.
The factory access code is: 1234. You can change it in this menu.
You can access 3 sub-menus by typing the corresponding number:
(M) 1: DESIGNATIONS
(M) 2: OPERATION
(M) 3: SYSTEM PARAMETERS
(M) 1. DESIGNATIONS
(M) 1.1 SITE NAME
1 1 (M) 1.1
This sub-menu allows you to set the name of the site or of the digital unit itself in the event that several
digital units are used in the same installation.
(M) 1.2 CABLE NAME
1 2 1 (M)
1.2.1
The user may utilize up to 16 characters to assign a name to each sense cable. (Menu 1.2.1)
You can also associate a sense cable with the previous cable (Menu 1.2.2).
1 2 2 (M)
1.2.2
The association allows you to create a group of cables.
Within this group, the first cable is the Master and the subsequent cables are dependants.
The parameters for naming and assignment of relays that are applied to the Master cable will also be
applied to the dependent cables.
However, each sense cable retains its capacity to detect leaks and to independently issue alarms.
The location of the alarms, in metres, will no longer be performed in terms of the cable, but is
performed instead on the group.