24
AUTOPULSE Z-20 Agent Releasing Panel Operator’s Manual (579-1165AR)
Piezo Silence:
Tap Piezo Silence to access the Piezo Silence Menu screen, where
the On or Off buttons can be used to control the piezos at the panel
and turn the Remote Annunciator’s piezo on or off.
Cfig Download:
Tap Cfig Download to access the Configuration Menu screen.
Inside, the following functions are available:
1. Tap Enable to download a job to a remote panel.
2. Tap Enable All to download a job to all the remote panels.
3. Tap Disable to disable the job download option to a remote panel.
4. Tap Revert to access the following functions:
Ta p Alt Cfig to access the details of the last job used by the
panel.
Tap Swap to swap the current job for the one used by the panel
last.
Ta p NoSwap to move back to the Configuration Menu screen.
Earth Fault Search:
Tap Earth Fault Search to access the Earth Fault Search? screen,
which can be used to test for earth faults in the circuit. The following
functions are available:
• Tap Location to display a list of cards that can be tested for
earth faults.
• Tap IDNet to display a list of IDNet channels that can be tested
for earth faults.
• Tap LastResults to view the results of the last earth fault test.
Continued on next page
Piezo Silence Menu
Off On
USER
BUTTON 1
USER
BUTTON 2
USER
BUTTON 3
Configuration Menu
Enable Enable All
USER
BUTTON 1
USER
BUTTON 2
USER
BUTTON 3
Disable
Revert
Date
Time
Earth Fault Search?
Location IDNet
USER
BUTTON 1
USER
BUTTON 2
USER
BUTTON 3
LastResult
Date
Time
Diagnostics, Continued