28
 AUTOPULSE Z-20 Agent Releasing Panel Operator’s Manual (579-1165AR)
TrueAlarm Service:
Tap   TrueAlarm Service to generate a report which contains the following information:
• Device Number
• Custom Label
• Alarm Level (sensitivity level of the device)
• Average Value
• Current Value
• Percent of Alarm: Shows the current value for the sensor. Value is shown as a percentage of 100% (alarm). For 
example, if the value shown is 9%, it means that the sensor is currently at 9% of the value required to trigger an 
alarm.
• Peak Value: Shows the highest value that the sensor has reached. Value is shown as a percentage of 100% 
(alarm). For example, if the value shown is 9%, it means that the peak value experienced by the sensor was 9% of 
the value required to trigger an alarm.
• Current State: Possible values include Normal, Trouble, Dirty, Excessively Dirty, and Almost Dirty.
TrueAlarm CO:
Tap   TrueAlarm CO to generate a report with the following information regarding the TrueAlarm CO devices:
• Device Number (on the network)
• Custom Label (custom description of the device)
• Current Device Value (PPM)
• End-of-Life Date
• Device Status (Normal, Trouble)
Active List:
Tap  Active List to access the Print Active List screen, where the Install Mode button can be used to generate a report 
containing the following Install Mode list information:
• Point ID
• Custom Label
• Device Status
Verification Tally:
Tap   Verification Tally to generate a report containing the following information for each device supporting the alarm 
verification:
• Device Number
• Custom Label
• Device Type
• Point Type
• Tally Count
Report Menu, Continued