I. Normal conditions:
•  The Stop Valve (B) is opened and 
locked
•  The Main Drain Valve (D) and System 
Drain Valve (E) are closed
•  The Diaphragm Supply Valve (P) and 
Alarm Control Valve (H) are open
•  The Manual Control Station (M) and 
Alarm Test Valve (G) are closed
•  Water Supply Gauge (J) reads the 
upstream water pressure
•  The System Gauge (L) reads zero
•  The Diaphragm Gauge (K) is equal 
to or greater than the Water Supply 
Gauge (J)
II. Operation
When set for service, the DV-5 Dia-
phragm Chamber is pressurized from 
the inlet side of the Stop Valve (B). 
Opening of the Manual Control Station 
(M) or the Solenoid Valve (R) upon fire 
detection releases water from the Dia-
phragm Chamber faster than it can 
be replenished through the Automatic 
Shut-Off Valve (N). The water supply 
pressure then forces the DV-5 Dia-
phragm open permitting water to flow 
into the system piping, as well as to the 
Waterflow Switch (C).
III. Removing system from service:
Step 1. Close the Diaphragm Supply 
Valve (P).
Step 2. Close the Stop Valve (B).
Step 3. Open the Main Drain Valve (D). 
IV. Placing the system back in 
service:
Step 1. Close the Stop Valve (B).
Step 2. Close the Diaphragm Supply 
Valve (P).
Step 3. Open the Main Drain Valve (D), 
System Drain Valve (E), and all auxil-
iary drains in the system. Close the 
System Drain Valve (E) and auxiliary 
drain valves after water ceases to dis-
charge. Leave the Main Drain Valve (D) 
open.
Step 4. Depress the plunger of the 
Automatic Drain Valve (F) to verify that 
it is open and that the DV-5 Valve is 
completely drained.
Step 5. Clean the Diaphragm Supply 
Strainer (Q).
Step 6. Reset the actuation system.
Manual Actuation — Push the operat-
ing lever up; however, do not close the 
hinged cover at this time.
Electric Actuation — Reset the electric 
detection system to de-energize the 
Solenoid Valve (R).
Step 7. Open the Diaphragm Supply 
Valve (P) to pressurize the DV-5 Dia-
phragm Chamber.
Step 8. Open and then close the 
Manual Control Station (M) to vent 
trapped air from the DV-5 Diaphragm 
Chamber.
Step 9. Temporarily close the Dia-
phragm Supply Valve (P), and then 
observe the Diaphragm Gauge (K) for 
a drop in pressure.
If the Diaphragm Chamber Pressure 
Gauge (K) indicates no drop in pres-
sure, re-open the Diaphragm Supply 
Valve (P) and proceed to the next step. 
Step 10. Partially open the Stop Valve 
(B), close the Main Drain Valve (D), and 
observe the Automatic Drain Valve (F) 
for leaks. If there are no leaks, the DV-5 
Valve is ready to be placed in service 
and the Stop Valve must then be fully 
opened.
V. Weekly test:
Important: Prior to closing any valves 
or activating any alarms, notify local 
security guards and the central alarm 
station if applicable.
Step 1. Open the Alarm Test Valve (G), 
verify that the alarm signal created by 
the Waterflow Switch (C) is visible at 
the fire panel. If applicable, check the 
sound of the water motor alarm — it 
must be clear and steady.
Step 2. Return the Alarm Test Valve (G) 
to the normally closed position after 
verifying that the alarm signal is visible 
at the fire panel.
Step 3. Drain the alarm line by squeez-
ing the Automatic Drain Valve (F). If the 
supply is below the normal, use the 
instructions from the water supply to 
obtain the usual pressure.
Water Motor Alarm Connection
Diaphragm Supply Connection
Stop Valve
Water Supply Gauge
Manual Control Station
Diaphragm Supply Valve
Automatic Shut-Off Valve
Diaphragm Supply Strainer
Automatic Drain Valve
Diaphragm Gauge
Solenoid Valve
System Gauge
Waterow Switch
System Drain Valve
Main Drain Valve
Alarm Test Valve
Alarm Control Valve
Description
DV-5 Valve
Item
B
D
E
C
A
G
H
K
J
M
N
R
Q
P
L
1
2
F
B
Q
P
1
C
G
2
H
F
J
D
E
L
N
A
R
M
K
Appendix C of TFP1335 (12/2016) 
Summary Instructions (If problems occur, consult full document) 
Deluge Valve, DV-5, DN40 thru DN200, Electric Actuation