TFP1335
Page 5 of 26
Wet Pilot
Actuation
The Wet Pilot Actuation Trim forms a
part of the laboratory approval of the
DV-5 Valves and is necessary for their
proper operation.
The Wet Pilot Actuation Trim provides
for connection of a detection system
consisting of wet pilot line sprinklers
(heat detectors) and manual control
stations interconnected with minimum
DN15 steel pipe. The pilot line is con-
nected to the Wet Pilot Line Connection
shown in Figure 4.
Installation dimensions are provided in
Figure 19.
Pilot sprinklers are to be minimum 80
K-factor orifice approved automatic
sprinklers. Manual Control Stations
are to be the Model MC-1 described in
Technical Data Sheet TFP1382.
The maximum height of a wet pilot line
above the DV-5 Valve must not exceed
the limitations shown in Table B as a
function of the minimum water supply
pressure to the DV-5 Valve for an equiv-
alent length (pipe plus fittings) of the
pilot line up to 150 meters to the most
remote pilot sprinkler.
Provision must be made for install-
ing a 80 K-factor orifice, Inspector’s
Test Connection at the most hydrauli-
cally demanding location of a wet pilot
line (usually adjacent to the highest
and most remote wet pilot sprinkler or
manual control station).
NOTES: Wet Pilot Lines must be main-
tained at a minimum temperature of
4°C.
At a minimum, it is recommended that
internally galvanized pipe and cast iron
fittings be used for wet pilot lines.
Diaphragm Supply Connection
Water Motor Alarm Connection
Wet Pilot Line Connection
Automatic Shut-Off Valve
Diaphragm Supply Strainer
Stop Valve
Diaphragm Gauge
Manual Control Station
Diaphragm Supply Valve
System Gauge
Main Drain Valve
System Drain Valve
Waterow Switch
Alarm Test Valve
Alarm Control Valve
Water Supply Gauge
Automatic Drain Valve
Description
DV-5 Valve
B
1
P
Q
C
G
2
H
F
J
D
N
A
3
E
L
1
2
3
B
K
M
N
Q
P
M
L
K
F
G
H
J
D
E
C
Item
A
FIGURE 4
WET PILOT ACTUATION
(Refer to Figures 7 thru 10 for specific Bills of Material)