TABLE A
PRINCIPAL COMPONENTS
TECHNICAL DATA SHEETS AND LABORATORY APPROVALS
TABLE B
60 HZ AIR COMPRESSOR SELECTION CRITERIA
FOR DELUGE DRY SYSTEM ARRANGEMENTS
BASED ON SYSTEM TYPE AND VOLUME
Description Model TDS
*
UL C-UL/ULC FM
Automatic Water Control Valve and Deluge Trim
DV-5
A
Wet Pilot Actuation TFP1311 X X X
Dry Pilot Actuation TFP1316 X X X
Electric Actuation TFP1321 X X X
Remote-Resetting TFP1325 X X X
Remote-Resetting, Pressure-Reducing TFP1326 X X X
System Shut-Off Valve, 1 1/2 to 2 in. (DN40 to DN50) POWERBALL X
4
X
4
X
4
System Shut-Off Valve, 3 to 8 in. (DN75 to DN200) BFV-300 TFP1511 X X X
Pressure Alarm Switch, POTTER PS10-2A X
5
X
5
X
5
Pressure Alarm Switch, POTTER PS40-2A X
5
X
5
X
5
Control Panel, Potter Electric Signal
1
PFC-4410RC X
5
X
5
X
5
Air Maintenance Device
2
, Regulator Type AMD-1 TFP1221 X X X
Air Maintenance Device
3
, Switch Type AMD-2 TFP1231 X X X
Nitrogen Maintenance Device
3
AMD-3 TFP1241 X X X
Notes
1. The Model PFC-4410RC is standard. The Red-E Cabinet may be ordered without an integral control panel. Red-E Cabinets featuring remote-resetting and remote-resetting,
pressure-reducing system types are not offered with a control panel.
2. The Model AMD-1 Air Maintenance Device, in addition to an auxiliary air tank, is utilized as standard equipment for dry pilot actuation having a compressor that delivers air at
5.5 ft³/min (0.16 m³/min) or higher. In the case of dry pilot actuation, the automatic air supply is utilized for the air pressure required for the dry pilot lines.
An OL12516AC (1/6 HP) air compressor is provided as standard for maintaining the air pressure in the auxiliary air tank.
3. The Model AMD-2 Air Maintenance Device and Model AMD-3 Nitrogen Maintenance Device, as well as the Model AMD-1 Air Maintenance Device, are offered as options when
the Red-E Cabinet for Dry Pilot Actuation is ordered without a built-in automatic air supply (for example, air compressor).
4. Approvals under the name of LANSDALE VALVE & MANUFACTURING.
5. Approvals under the name of POTTER.
* TDS - Technical Data Sheet
Model
Number
Horsepower
Rating
(hp)
Voltage
1
Electric/Electric
Actuation
Electric/Pneumatic
Actuation
System Volume
@20 psi (1.38 bar) in 30 mins
gal (L)
System Volume
@40 psi (2.76 bar) in 30 mins
gal (L)
OL12516AC 1/6
115 VAC
60 Hz
290
(1095)
125
(473)
OL25033AC 1/3
115 VAC
60 Hz
475
(1795)
125
(945)
OL36550AC 1/2
115/230 VAC
60 Hz
780
(2950)
365
(1380)
OL43075AC 3/4
115/230 VAC
60 Hz
930
(3520)
430
(1625)
OL615100AC
2
1
115/230 VAC
60 Hz
1430
(5410)
615
(2325)
OL915100AC
2
1 1/2
115/230 VAC
60 Hz
2320
(8780)
915
(3460)
OL1225200AC
2
2
230 VAC
60 Hz
3040
(1150 0 )
1225
(4635)
Notes
1. Dry Pilot Actuation is provided as standard with a Model OL12516AC Air Compressor.
2. For 6 in. (DN150) and 8 in. (DN200) cabinets only.
TFP1301
Page 4 of 8