the affected fire protection systems
must first be obtained from the proper
authorities and all personnel who may
be affected by this decision must be
notified.
The TYCO Red-E Cabinet does not
require any regularly scheduled inspec-
tion or maintenance. The riser com-
ponents enclosed within the Red-E
Cabinet, however, must be main-
tained in accordance with their appli-
cable technical data sheet as shown in
Table A. In addition, the control panel
and automatic air supply (as applica-
ble) components must be maintained
in accordance with their applicable
instructions provided with the Red-E
Cabinet.
The owner is responsible for the inspec-
tion, testing, and maintenance of their
fire protection system and devices in
compliance with this document, as well
as with the applicable standards of any
authorities having jurisdiction. Contact
the installing contractor or product
manufacturer with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested,
and maintained by a qualified Inspec-
tion Service in accordance with local
requirements and/or national codes.
Installation
The TYCO DV-5A Red-E Cabinet is to
be installed following the directions
given in the Red-E Cabinet Install-
er’s Manual provided with the Red-E
Cabinet. Instructions pertain to the fol-
lowing items:
Placing the cabinet
Connecting the system piping
Electrical connections
System start-up
Care and
Maintenance
Inspection, testing, and maintenance
must be performed in accordance
with the requirements of the NFPA, and
any impairment must be immediately
corrected.
Before closing a fire protection system
main control valve for maintenance
work on the fire protection system that
it controls, permission to shut down
Red-E Cabinet
Technical
Support
Technical support for the Red-E
Cabinet is available by calling 888-572-
4638 during regular business hours of
8:30-12:00 and 1:00-5:00 Eastern Time
Monday through Friday.
Contact Red-E Cabinet Technical
Support for special request cabinet
configuration or electrical connection/
control panel programming inquiries.
An answering service will take mes-
sages outside of the regular business
hours.
TABLE C
50 HZ AIR COMPRESSOR SELECTION CRITERIA
FOR DELUGE DRY SYSTEM ARRANGEMENTS
BASED ON SYSTEM TYPE AND VOLUME
Model
Number
Power
Rating
(kW)
60 Hz Model
Equivalent
Horsepower
Rating
1
(hp)
Voltage
Electric/Electric
Actuation
Electric/Pneumatic
Actuation
System Volume
@20 psi (1.36 bar) in 30 mins
gal (L)
System Volume
@40 psi (2.76 bar) in 30 mins
gal (L)
OL39012AC-50 0.12 1/6
220 VAC
50 Hz
276
(1048)
103
(473)
OL75025AC-50 0.25 1/3
220 VAC
50 Hz
465
(1762)
198
(750)
OL114056AC-50 0.56 1/2
220 VAC
50 Hz
759
(2874)
301
(1140)
OL135075AC-50 0.75 3/4
220 VAC
50 Hz
989
(3743)
357
(1350)
OL1965120AC-50
2
1.2 1
220 VAC
50 Hz
517
(1956)
OL2870150AC-50
2
1.5 1 1/2
220 VAC
50 Hz
758
(2870)
OL3840200AC-50
2
2 2
220 VAC
50 Hz
1014
(3840)
Notes
1. Denotes the equivalent model of 60 Hz compressor for part number use. Must specically request 50 Hz in ordering process. HP model equivalent is not a direct conversion to
kW. Actual conversion from kilowatts (kW) to horsepower units (hp) is based on 1 kW = 1.34102 hp.
2. For 6 in. (DN150) and 8 in. (DN200) cabinets only.
TFP1301
Page 5 of 8