Installation
TYCO Series LFII Residential 4.9K 
Pendent and Recessed Pendent Sprin-
klers must be installed in accordance 
with this section.
General Instructions
Do not install any bulb type sprinkler 
if the bulb is cracked or there is a loss 
of liquid from the bulb. With the sprin-
kler held horizontally, a small air bubble 
should be present. The diameter of the 
air bubble is approximately 1/16 in. 
(1,6 mm).
A leak-tight 1/2 in. NPT sprinkler 
joint should be obtained by apply-
ing a minimum-to-maximum torque of 
7 to 14 lb-ft (9,5 to 19,0 N∙m). Higher 
levels of torque can distort the sprin-
kler Inlet with consequent leakage or 
impairment of the sprinkler.
Do not attempt to compensate for 
insufficient adjustment in an Escutch-
eon Plate by under- or over- tightening 
the sprinkler. Re-adjust the position of 
the sprinkler fitting to suit.
Pendent Sprinklers
The Series LFII Residential Pendent 
Sprinklers must be installed in accor-
dance with the following instructions.
Step 1. Install pendent sprinklers in the 
pendent position with the deflector par-
allel to the ceiling.
Step 2. With pipe thread sealant 
applied to the pipe threads, hand-
tighten the sprinkler into the sprinkler 
fitting.
Step 3. Tighten the sprinkler into the 
sprinkler fitting using only the W-Type 
6 Sprinkler Wrench, as shown in Figure 
4. With reference to Figure 1, apply 
the W-Type 6 Sprinkler Wrench to the 
wrench flats.
Recessed Pendent Sprinklers
The Series LFII Residential Recessed 
Pendent Sprinklers must be installed 
in accordance with the following 
instructions.
Step A. Install the recessed pendent 
sprinklers in the pendent position with 
the deflector parallel to the ceiling.
Step B. After installing either the 
Style 15 or the Style 20 Mounting Plate 
over the sprinkler threads, and with 
pipe thread sealant applied to the pipe 
threads, hand-tighten the sprinkler into 
the sprinkler fitting.
Step C. Tighten the sprinkler into the 
sprinkler fitting using only the W-Type 7 
Recessed Sprinkler Wrench, as shown 
in Figure 5. With reference to Figure 1, 
apply the W-Type 7 Recessed Sprinkler 
Wrench to the sprinkler wrench flats.
Step D. After the ceiling has been 
installed, or the finish coat has been 
applied, slide on either the Style 15 
Closure or the Style 20 Closure over the 
Series LFII Residential Sprinkler and 
push the Closure over the Mounting 
Plate until its flange comes in contact 
with the ceiling.
Care and 
Maintenance
TYCO Series LFII Residential 4.9K 
Pendent and Recessed Pendent Sprin-
klers must be maintained and serviced 
in accordance with this section.
Before closing a fire protection system 
main control valve for maintenance 
work on the fire protection system that 
it controls, permission to shut down the 
affected fire protection system must be 
obtained from the proper authorities 
and notify all personnel who may be 
affected by this action.
Absence of the outer piece of an 
escutcheon, which is used to cover 
a clearance hole, can delay sprinkler 
operation in a fire situation.
The owner must assure that the sprin-
klers are not used for hanging any 
objects and that the sprinklers are only 
cleaned by means of gently dusting 
with a feather duster; otherwise, non-
operation in the event of a fire or inad-
vertent operation may result.
Sprinklers which are found to be 
leaking or exhibiting visible signs of 
corrosion must be replaced.
Automatic sprinklers must never be 
painted, plated, coated, or other-
wise altered after leaving the factory. 
Modified sprinklers must be replaced. 
Sprinklers that have been exposed to 
corrosive products of combustion, but 
have not operated, should be replaced 
if they cannot be completely cleaned 
by wiping the sprinkler with a cloth or 
by brushing it with a soft bristle brush.
Care must be exercised to avoid 
damage to the sprinklers before, 
during, and after installation. Sprin-
klers damaged by dropping, striking, 
wrench twist/slippage, or the like, must 
be replaced. Also, replace any sprinkler 
that has a cracked bulb or that has lost 
liquid from its bulb. See the Installation 
section.
The owner is responsible for the inspec-
tion, testing, and maintenance of their 
fire protection system and devices in 
compliance with this document, as well 
as with the applicable standards of the 
NATIONAL FIRE PROTECTION ASSO-
CIATION, such as NFPA 25, in addi-
tion to the standards of any authorities 
having jurisdiction. Contact the install-
ing contractor or product manufacturer 
with any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested, 
and maintained by a qualified Inspec-
tion Service in accordance with local 
requirements and/or national codes.
Limited 
Warranty
For warranty terms and conditions, visit 
www.tyco-fire.com.
Ordering 
Procedure
Contact your local distributor for avail-
ability. When placing an order, indicate 
the full product name and part number 
(P/N).
Sprinkler Assemblies
Specify: Series LFII 4.9K Residential 
Pendent Sprinkler (TY2236), (specify 
temperature rating), with (specify) finish, 
P/N (specify):
155°F (68°C)
Natural Brass ................. 51-212-1-155
Pure White (RAL 9010)
Polyester
1, 2
 ..................51-212-3-155
Signal White (RAL 9003)
Polyester
1
....................51-212-4-155
Jet Black (RAL 9005)
Polyester
1
....................51-212-5-155
Chrome Plated................51-212-9-155
175°F (79°C )
Natural Brass ..................51-212-1-175
Pure White (RAL 9010)
Polyester
1, 2
 .................. 51-212-3-175
Signal White (RAL 9003)
Polyester
1
.................... 51-212-4-175
Jet Black (RAL 9005)
Polyester
1
.................... 51-212-5-175
Chrome Plated. . . . . . . . . . . . . . . .  51-212-9-175
1.  UL Listed as corrosion-resistant.
2.  Eastern Hemisphere sales only.
Recessed Escutcheon
Specify: Style 15 Escutcheon with 
(specify*) finish, P/N (specify*) or 
Style 20 Recessed Escutcheon with 
(specify*) finish, P/N (specify*)
* Refer to Technical Data Sheet TFP770.
Sprinkler Wrenches
Specify: W-Type 6 Sprinkler Wrench, 
P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench, 
P/N 56-850-4-001