TFP403
Page 3 of 4
Technical 
Data
Approvals
UL and C-UL Listed
Certified to all requirements of 
NSF/ANSI 61
Note: Sprinklers with a polyester finish are 
UL Listed as corrosion-resistant sprinklers.
See the Design Criteria section for details 
on these approvals.
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K=4.9 gpm/psi
½
 (70,6 lpm/bar
½
)
Temperature Rating
155°F (68°C) or 175°F (79°C)
Finishes
Natural Brass, Pure White Polyester 
Coated, Signal White Polyester Coated, 
Jet Black Polyester Coated, or Chrome 
Plated
Physical Characteristics
Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass 
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . Copper 
Sealing Assembly ..Beryllium Nickel w/TEFLON 
Bulb (3 mm) . . . . . . . . . . . . . . . . . . . . . . . .   Glass  
Compression Screw . . . . . . . . . . . . . . . . .Bronze  
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze 
Operation
The glass bulb contains a fluid that 
expands when exposed to heat. When 
the rated temperature is reached, the 
fluid expands sufficiently to shatter the 
glass bulb, allowing the sprinkler to 
activate and flow water.
Design 
Criteria
The TYCO Series LFII Residential 4.9K 
Pendent and Recessed Pendent Sprin-
klers are UL and C-UL Listed for instal-
lation in accordance with this section.
Residential Sprinkler 
Design Guide
When conditions exist that are outside 
the scope of the provided criteria, refer 
to the Residential Sprinkler Design 
Guide TFP490 for the manufactur-
er's recommendations that may be 
acceptable to the local authority having 
jurisdiction.
System Types
Per the UL Listing and the C-UL Listing, 
wet pipe systems may be utilized.
Ceiling Types
Smooth flat horizontal, or beamed, or 
sloped, in accordance with the 2013 
Edition of NFPA 13D, 13R, or 13, as 
applicable.
Hydraulic Design 
(NFPA 13D and 13R)
For systems designed to NFPA 13D or 
NFPA 13R, the minimum re quired sprin-
kler flow rates are given in Table A as a 
function of temperature rating and the 
maximum allowable coverage areas. 
The sprinkler flow rate is the minimum 
required discharge from each of the 
total number of design sprinklers as 
specified in NFPA 13D or NFPA 13R.
Hydraulic Design 
(NFPA 13)
For systems designed to NFPA 13, the 
number of design sprinklers is to be 
the four most hydraulically demanding 
sprinklers. The minimum required dis-
charge from each of the four sprinklers 
is to be the greater of the following:
•  The ow rates given in Table A as a 
function of temperature rating and 
the maximum allowable coverage 
area.
• 
A minimum discharge of 0.1 gpm/ft² 
over the design area comprised 
of the four most hydraulically 
demanding sprinklers for actual 
coverage areas protected by the 
four sprinklers.
Obstruction to  
Water Distribution
Sprinklers are to be located in accor-
dance with the obstruction rules of 
NFPA 13D, 13R, and 13 as applicable 
for residential sprinklers as well as with 
the obstruction criteria described within 
the Technical Data Sheet TFP490.
Operational Sensitivity
Sprinklers are to be installed with a 
deflector-to-ceiling distance of 1 1/4 in. 
to 4 in.
Sprinkler Spacing
The minimum spacing between sprin-
klers is 8 ft (2,4 m). The maximum 
spacing between sprinklers cannot 
exceed the length of the coverage 
area (Table A) being hydraulically calcu-
lated, for example, maximum 12 ft for a 
12 ft x 12 ft coverage area, or 20 ft for 
a 20 ft x 20 ft coverage area.
Maximum 
Coverage 
Area 
(1)
ft x ft 
(m x m)
WET PIPE SYSTEM
Minimum Flow and Residual Pressure 
(2)(3)
Ordinary Temperature Rating 
155°F (68°C)
Intermediate Temperature Rating 
175°F (79°C)
Deflector to 
Ceiling
Installation 
Type
Minimum 
Spacing
ft 
(m)
Flow 
gpm 
(l/min)
Pressure 
psi  
(bar)
Flow 
gpm 
(l/min)
Pressure 
psi  
(bar)
12 x 12 
(3,7 x 3,7)
13 
(49,2)
7.0  
(0,48)
13 
(49,2)
7.0  
(0,48)
Smooth  
Ceilings  
1-1/4 in. to 4 in.
Beamed  
Ceilings per 
NFPA 13D  
or 13R 
1-1/4 in. to 
1-3/4 in. below 
bottom of 
beam.
Recessed us-
ing either Style 
15 or Style 20 
Escutcheon or 
non-recessed 
per NFPA 13D, 
13R, or 13
8
(2,4)
14 x 14 
(4,3 x 4,3)
13 
(49,2)
7.0  
(0,48)
13 
(49,2)
7.0  
(0,48)
16 x 16 
(4,9 x 4,9)
13 
(49,2)
7.0  
(0,48)
13 
(49,2)
7.0  
(0,48)
18 x 18 
(5,5 x 5,5)
17 
(64,3)
12.0 
(0,83)
17 
(64,3)
12.0 
(0,83)
20 x 20 
(6,1 x 6 ,1)
20 
(75,7)
16.7 
(1,15)
20 
(75,7)
16.7 
(1,15)
Notes:
1.  For coverage area dimensions less than or between those indicated, use the minimum required ow for the next highest coverage area for which hydraulic design 
criteria are stated.
2.  Requirement is based on minimum ow in gpm (lpm) from each sprinkler. The associated residual pressures are calculated using the nominal K-factor. See Hydraulic 
Design under the Design Criteria section.
3.  For NFPA 13 residential applications, the greater of 0.1 gpm/ft
2
 over the design area or the ow in accordance with the criteria in this table must be used.
TABLE A 
WET PIPE SYSTEM 
SERIES LFII RESIDENTIAL 4.9K PENDENT AND RECESSED PENDENT SPRINKLERS (TY2236) 
NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA