UniPOS Fire Control Panel FS5200
Instruction manual Page 10
Revision 8/07.17 of 69
Option to prolong the time period for Fire condition stage I with programmable overall
inspection period
Built-in sounder for fire condition – one tonal, continuous, can be switched off
Built-in sounder for fault condition – one tonal, discontinuous, can be switched off
Built-in real time clock
Set of test modes and options for adjustment :
Setting the clock;
Check up of light and sound indications;
Test of fire alarm lines;
Adjustment of outputs and the integrated external devices;
Measuring the current value in the fire alarm lines;
Programming of parameters and modes of operation;
Remote programming of the parameters from a distant operator control point.
Energy independent archive of registered events with the events type, date and hour –
up to 2500 events
Communication interface for external devices - RS-232 (directly or via modem) or RS-
485.
4.8. Indications of registered events
Light indication - LED
Text messages - LCD display -
4 lines x 20 symbols each,
Latin/Cyrillic characters, backlit
Sound - built-in sounder
4.9. Power supply
4.9.1. Mains
voltage - 220/230V
frequency - 50Hz
4.9.2. Backup batteries
battery type - lead, gel electrolyte
number of batteries - 2 pcs
connection - serial connection
nominal voltage of the backup battery - 24V
nominal capacity C
20
- 12Ah
extreme discharge voltage - 21V
charge voltage - 28,2V
4.9.3. Consumption on backup batteries supply
Configuration 00 - < 155mA at 24V
- < 150mA at 26V
Configuration 03 - < 235mA at 24V
- < 225mA at 26V
Configuration 06 - < 320mA at 24V
- < 305mA at 26V
Configuration 09 - < 400mA at 24V
- < 380mA at 26V
4.9.4. Power supply to external devices
voltage - (24±5)V
maximum current value (including current
of controllable outputs) - 1,5А