EasyManua.ls Logo

USFilter V-2000 - Page 6

Default Icon
126 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IM 25.055AC UA (C/6-01)
AUTOMATIC CHLORINATOR - 3000LB/24HR
VERY IMPORTANT SAFETY PRECAUTIONS - CHLORINE (CONT’D)
WHEN ANY CONNECTION IS BROKEN EVEN FOR A SHORT TIME, IMMEDIATELY PLUG
THE RESULTANT OPENINGS WITH A RUBBER STOPPER OR EQUIVALENT TO PREVENT
THE ENTRANCE OF MOISTURE. MOISTURE MUST BE EXCLUDED FROM ANY PART OF
THE EQUIPMENT THAT IS NORMALLY EXPOSED TO DRY CHLORINE ONLY. WHILE DRY
CHLORINE IS NON-CORROSIVE, MOIST CHLORINE IS EXTREMELY CORROSIVE TO COM-
MON METALS, SUCH AS BRASS OR STEEL.
THE TWO MOST COMMON CAUSES OF CHLORINE PIPING LEAKS ARE:
1. RE-USE OF GASKETS. THIS SHOULD NEVER BE DONE. ALWAYS HAVE AN AD-
EQUATE SUPPLY ON HAND AND ALWAYS USE NEW GASKETS OF THE CORRECT
MATERIAL AND SIZE AS IDENTIFIED ON THE EQUIPMENT PARTS DRAWING.
2. IMPROPERLY MADE-UP THREADED PIPE JOINTS. SEE CHLORINE GAS HAN-
DLING MANUAL FOR RECOMMENDED PROCEDURE.
EXCEPT IN CASES OF LEAK DETECTION OR CALIBRATION ADJUSTMENTS, THE CHLO-
RINE GAS SUPPLY MUST BE SHUT OFF AT THE GAS SUPPLY CONTAINERS AND THE CHLO-
RINE GAS IN THE SYSTEM EXHAUSTED BEFORE SERVICING THE EQUIPMENT.
USE ONLY USF/W&T LISTED PARTS, EXCEPT FOR COMMERCIALLY AVAILABLE PARTS
AS IDENTIFIED ON THE PARTS LIST. THE USE OF UNLISTED PARTS CAN RESULT IN EQUIP-
MENT MALFUNCTIONS HAVE HAZARDOUS CONSEQUENCES.
DO NOT DISCARD THIS INSTRUCTION BOOK UPON COMPLETION OF INSTALLATION.
INFORMATION PROVIDED IS ESSENTIAL TO PROPER AND SAFE OPERATION AND MAIN-
TENANCE.
ADDITIONAL OR REPLACEMENT COPIES OF THIS BOOK ARE AVAILABLE FROM:
USFILTER'S WALLACE & TIERNAN PRODUCTS
1901 WEST GARDEN ROAD
VINELAND, NEW JERSEY 08360
PHONE: (856) 507-9000
FAX: (856) 507-4125
NOTE
Minor part number changes may be incorporated into USF/W&T products from time to time that are
not immediately reflected in the instruction book. If such a change has apparently been made in your
equipment and does not appear to be reflected in your instruction book, contact your local USF/W&T
sales representative for information.
Please include the equipment serial number in all correspondence. It is essential for effective communi-
cation and proper equipment identification.
1.010-41