ENGLISH
16
INSTALLATION
Installation of the control unit, the safety devices and
accessories must be performed with the power
supply disconnected.
POWER SUPPLY
The control unit must be powered by means of a
230 V - 50 Hz or 120 V - 60 Hz power line,
depending on the model, protected by a differential
magnetothermal switch in compliance with legal
regulations.
Connect the power cables to the control unit L and
N terminals.
MOTOR
The control unit can control one asynchronous AC
motor.
Connect the cables for motor as follows:
• Opening cable to terminal C1
• Closing cable to terminal C3
• Common return cable to terminal C2
• Start-up capacitor between terminals C1 and C3
BLINKER
The control unit provides for the use of a 230V -
40W or 120V - 40W blinker with built-in
intermittence.
Connect the cables to terminals D3 and D4.
COURTESY LIGHT
This output has a normally-open clean contact relay
which closes for approx. 1 second at the start of an
opening phase. This switch may be used to activate
a courtesy light timer (max. load: 230V - 4 A).
PLEASE NOTE: If there is no timer, the courtesy
light can be controlled using channel 4 of receiver
MR1: bistable or timer programmable channel (read
the instructions for the receiver MR1 thoroughly).
The switch is on terminals D1 and D2.