Code Parameter Range Step Default Custom Description Page
2. 6 U
in
signal range 02 1 0 0 = 010 V
1 = Custom setting range
2 = -10+10 V (can be used with
Joystick control only)
2
. .
. .
. 7U
in
custom setting min. 0100% 0.01% 0.00% 22
2
. .
. .
. 8U
in
custom setting max. 0100% 0.01% 100.00% 22
2
. .
. .
. 9U
in
signal inversion
0
1
1 0 0 = Not inverted 22
1 = Inverted
2
..
..
. 10 U
in
signal filter time
0 10s
0.01s 0.1s 0 = No filtering 22
2
..
..
. 11 I
in
signal range 0210 0 = 020 mA 23
1 = 420 mA
2 = Custom setting range
2
..
..
. 12 I
in
custom setting minim. 0100% 0.01% 0.00% 23
2
..
..
. 13 I
in
custom setting maxim. 0100% 0.01% 100.00% 23
2
..
..
. 14 I
in
signal inversion
0
1
1 0 0 = Not inverted 23
1 = Inverted
2
. .
. .
. 15 I
in
signal filter time
0 10s
0.01s 0.1s 0 = No filtering 23
2
..
..
. 16 U
in
minimum scaling -320,00% 0% 0,01 0% = no minimum scaling 23
+320,00 %
2
..
..
. 17 U
in
maximum scaling -320,00% 100% 0,01 100% = no maximum scaling 23
+320,00 %
2
..
..
. 18 I
in
minimum scaling -320,00% 0% 0,01 0% = no minimum scaling 23
+320,00 %
2
..
..
. 19 I
in
maximum scaling -320,00% 100% 0,01 100% = no maximum scaling 23
+320,00 %
2
. .
. .
. 20 Free analogue input, 05 1 0 0 = Not use 24
signal selection 1 = U
in
(analogue voltage input)
2 = I
in
(analogue current input)
3 = Ain1 (option board)
4 = Ain2 (option board)
5 = Fieldbus signal
2
..
..
. 21 Free analogue input, 04 1 0 0 = No function 24
function 1 = Reduces current limit
(par. 1
..
..
.7)
2 = Reduces DC-braking current
3 = Reduces acc. and decel. times
4 = Reduces torque supervis. limit
2
..
..
. 22 Motorised potentiometer 0.12000.0 0.1 10.0 25
ramp time Hz/s Hz/s Hz/s
2
. .
. .
. 23 Option board Ain1 signal 01 1 0 0 = Not inverted 25
inversion 1 = Inverted
2
..
..
. 24 Option board Ain1 signal 010s 0.01s 0.1s 0 = No filtering 25
filter time
2
..
..
. 25 Option board Ain2 signal 0210 0 = 020 mA 25
signal range 1 = 420 mA
2 = 010 V
2
..
..
. 26 Option board Ain2 signal 01 1 0 0 = Not inverted 25
inversion 1 = Inverted
2
. .
. .
. 27 Option board Ain2 signal 0 10s 0.01s 0.1s 0 = No filtering 25
filter time
Note! Note!
Note! Note!
Note!
STOP
STOPSTOP
STOP
= Parameter value can be changed only when the frequency converter is stopped. (Continues)