Code Parameter Range Step Default Custom Description Page
3
..
..
. 13 Torque limit 0—2 1 0 0 = No 28
supervision function 1 = Low limit
2 = High limit
3
..
..
. 14 Torque limit 0—200% 1% 100% 28
supervision value xT
nCX
3
..
..
. 15 Reference limit 0—2 1 0 0 = No 28
supervision function 1 = Low limit
2 = High limit
3
..
..
. 16 Reference limit 0—f
max
0.1 Hz 0 Hz 28
supervision value (par. 1
..
..
. 2)
3
..
..
. 17 Extern. brake Off-delay 0—100.0 s 0.1 s 0.5 s 28
3
..
..
. 18 Extern. brake On-delay 0—100.0 s 0.1 s 1.5 s 28
3
..
..
. 19 Frequency converter 0—2 1 0 0 = No 28
temperature limit 1 = Low limit
supervision function 2 = High limit
3
..
..
. 20 Frequency converter -10—+75°C1°C +40°C28
temperature limit value
3
..
..
. 21 I/O-expander board (opt.) 0—14 1 3 See parameter 3
..
..
. 1 –
analogue output content
3
..
..
. 22 I/O-expander board (opt.) 0.01—10 s 0.01 1.00 See parameter 3
..
..
. 2 –
analogue output filter time
3
..
..
. 23 I/O-expander board (opt.) 0—1 1 0 See parameter 3
..
..
. 3 –
analogue output inversion
3
..
..
. 24 I/O-expander board (opt.) 0—1 1 0 See parameter 3
..
..
. 4 –
analogue output minimum
3
..
..
. 25 I/O-expander board (opt.) 10—1000% 1 100% See parameter 3
..
..
. 5 –
analogue output scale
3. 26 Analog output offset -100— 1 100% 29
(basic control board) 100,0%
3. 27 I/O-expander board (opt.) -100— 1 100% 29
analogue output offset +100,0%
3
..
..
. 28 Digital output DO1 0—320,00s 0,01 0,00 0,00 = delay not in use 29
on delay
3
..
..
. 29 Digital output DO1 0—320,00s 0,01 0,00 0,00 = delay not in use 29
off delay
3
..
..
. 30 Relay output RO1 0—320,00s 0,01 0,00 0,00 = delay not in use 29
on delay
3
..
..
. 31 Relay output RO1 0—320,00s 0,01 0,00 0,00 = delay not in use 29
off delay
3
..
..
. 32 Relay output RO1 0—320,00s 0,01 0,00 0,00 = delay not in use 29
on delay
3.33 Relay output RO2 0—320,00s 0,01 0,00 0,00 = delay not in use 29
off delay