EasyManua.ls Logo

Vacon NXI Series - Fuses, Nxi_Xxxx 5

Vacon NXI Series
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30 vacon cabling and connections
Tel: +358-201-2121 Fax: +358-201-212 205
6
6.1.1.3
Fuses, NXI_xxxx 5
Frame
Type
I
L
[A]
Bussman aR fuse
type
Fuse
size
Fuse
U
n
[V]
Fuse
I
n
[A]
No. of fuses
FR4
NXI_0004
4.3
170M1560
000
690
20
2
FR4
NXI_0009
9
170M1565
000
690
63
2
FR4
NXI_0012
12
170M1565
000
690
63
2
FR6
NXI_0016
16
170M1565
000
690
63
2
FR6
NXI_0022
22
170M1565
000
690
63
2
FR6
NXI_0031
31
170M1565
000
690
63
2
FR6
NXI_0038
38
170M1567
000
690
100
2
FR6
NXI_0045
45
170M1567
000
690
100
2
FR7
NXI_0061
61
170M1568
000
690
125
2
FR7
NXI_0072
72
170M1570
000
690
200
2
FR7
NXI_0087
87
170M1570
000
690
200
2
FR7
NXI_0105
105
170M1571
000
690
250
2
FR8
NXI_0140
140
170M3819
1
690
400
2
Table
6-2. Fuses used in Vacon NX (465 - 800V)
6.1.1.4
Fuses, NXI_xxxx 6
Frame
Type
I
L
[A]
Bussman aR fuse
type
Fuse
size
Fuse
U
n
[V]
Fuse
I
n
[A]
No. of fuses
FR6
NXI_0004
4.5
170M2673
00
1000
20
2
FR6
NXI_0005
5.5
170M2673
00
1000
20
2
FR6
NXI_0007
7.5
170M2673
00
1000
20
2
FR6
NXI_0010
10
170M2673
00
1000
20
2
FR6
NXI_0013
13.5
170M2679
00
1000
63
2
FR6
NXI_0018
18
170M2679
00
1000
63
2
FR6
NXI_0022
22
170M2679
00
1000
63
2
FR6
NXI_0027
27
170M2679
00
1000
63
2
FR6
NXI_0034
34
170M2683
00
1000
160
2
FR7
NXI_0041
41
170M2683
00
1000
160
2
FR7
NXI_0052
52
170M2683
00
1000
160
2
FR8
NXI_0062
62
170M4200
1SHT
1250
350
2
FR8
NXI_0080
80
170M4200
1SHT
1250
350
2
FR8
NXI_0100
100
170M4200
1SHT
1250
350
2
Table
6-3. Fuses used in Vacon NX (640 - 1100V)
Information about fuses
aR fuses protect the cables of the device against short-circuits.
gR fuses are designed to protect the device against both overcurrent and short-circuits.
gG fuses are generally used to protect cables against overcurrent and short-circuits.