EasyManua.ls Logo

Vacon NXI Series - Control Connections

Vacon NXI Series
90 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
cabling and connections vacon 39
24-hour support: +358-(0)40-8371 150 • Email: vacon@vacon.com
6
Dotted line indicates the connection with
inverted signal levels
24 V
GND
24 V
GND
U<+48V
I<50mA
+
0(4)/20mA
RL<500
Basic I/O board
NXOPTA1
+10Vref
AIA1+
GND
AIA2+
AIA2-
24Vout
GND
DIA1
DIA2
DIA3
CMA
24Vout
GND
DIB4
DIB5
DIB6
CMB
Iout+
Iout-
DO1
Reference
(voltage)
Reference
(current)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
6.2.1
Control connections
The basic control connections for boards A1 and A2/A3 are shown in Chapter 6.2.2.
The signal descriptions for the standard application are presented in Chapter 2 of the All in One
Application Manual. You can find the signal descriptions for other applications in the Vacon NX
Application Manual.
Figure
6-9. The I/O terminals
of the two basic boards
Figure
6-10. General wiring diagram of the basic I/O board
(NXOPTA1)
OPT-A2 OPT-A3
Board OPT-A1
in slot A
Boards OPT-A2 and
OPT-A3 in slot B
RO1/1
1/2
RO1/3
RO2/1
2/2
RO2/3
ac/dc
21
22
23
24
25
26
NX6_6.fh8
21
22
23
25
26
RO1/1
1/2
RO1/3
2/1
RO2/2
ac/dc
28
29
TI1+
TI1-
+t
Switching:
<8A/24Vdc,
<0.4A/125Vdc,
<2kVA/250Vac
Continuously:
< 2Arms
Basic relay board
OPT-A2
Switching:
<8A/24Vdc,
<0.4A/125Vdc,
<2kVA/250Vac
Continuously:
<2Arms
Basic relay board
OPT-A3

Related product manuals