7.3.3.3
Keypad direction
The keypad direction submenu (P3.3) displays and allows the operator to change the rotating
direction of the motor. This setting will not, however, influence the rotation direction of the motor
unless the keypad has been selected as the active control place.
See also Chapter 7.3.3.
7.3.3.4
Stop button activated
By default, pushing the STOP button will always stop the motor regardless of the selected control
place. You can disable this function by giving parameter 3.4 the value 0. If the value of this parameter
is 0, the STOP button will stop the motor only when the keypad has been selected as the active
control place.
Note: For additional information on controlling the motor with the keypad, see Chapters 7.2.1, 7.3.3 and
8.2.
NOTE!
There are some special functions that can be performed in menu M3:
Select the keypad as the active control place by pressing START for 3 seconds when the
motor is running. The keypad will become the active control place and the current
frequency reference and direction will be copied to the keypad.
Select the keypad as the active control place by pressing STOP for 3 seconds when the
motor is stopped. The keypad will become the active control place and the current
frequency reference and direction will be copied to the keypad.
Copy the frequency reference set elsewhere (I/O, fieldbus) to the panel by pressing
enter
for 3 seconds.
Note that if you are in any other than menu
M3
these functions will not work.
If you are in some other than menu
M3
and try to start the motor by pressing the START button
when the keypad is not selected as the active control place, you will get an error message:
Keypad
Control NOT ACTIVE
.