0020244997_07 Installation and maintenance instructions 57
Code Parameter Values or explanations
Factory
setting
Own setting
D.050 Offset min. speed In rpm, adjustment range: 0 to 3000 Nominal
value set in
factory
D.051 Offset max. speed In rpm, adjustment range: -990 to 0 Nominal
value set in
factory
D.058 Solar post-heating 0 = Solar post-heating deactivated
3 = DHW activation target value minimum 60 °C, thermo-
static mixing valve required between product and draw-
off point
0 = Solar
post-heating
deactivated
D.060 Number of safety therm. shut-
downs
Number of shutdowns Not ad-
justable
D.061 No. of shut-downs in ign. flame
controller
Number of unsuccessful ignitions in the last attempt Not ad-
justable
D.064 Avg. ignition time In seconds Not ad-
justable
D.065 Max. ignition time In seconds Not ad-
justable
D.067 Remaining anti-cycl. time for heat-
ing
In minutes Not ad-
justable
D.068 Number of first start attempts Number of unsuccessful ignitions Not ad-
justable
D.069 Number of second start attempts Number of unsuccessful ignitions Not ad-
justable
D.070 3-way valve operation 0 = Normal operating mode
1 = Parallel operation (mid-position)
2 = Permanent heating position
0 = Normal
operating
mode
D.071 Max. heating target flow temp. 40 to 80 75
D.072 Pump overrun after cylinder char-
ging
Adjustable from 010 minutes in increments of 1 minute 2 mins
D.073 Offset setting for comfort mode Adjustable from -15 K to 5 K 0
D.074 Anti-legionella funct. with integ-
rated cyl.
0 = Off
1 = On
1 = On
D.075 Max. cylinder charging time 2090 min 45 mins
D.076 Device Specific Number Device specific number = DSN
1 = VU 126/5-5 (H-GB) ecoTEC plus 612
3 = VU 156/5-5 (H-GB) ecoTEC plus 615
4 = VU 186/5-5 (H-GB) ecoTEC plus 618, VU 186/5-5
(P-GB) ecoTEC plus 618
9 = VU 246/5-5 (H-GB) ecoTEC plus 624
14 = VU 306/5-5 (H-GB) ecoTEC plus 630, VU 306/5-5
(P-GB) ecoTEC plus 630
20 = VU 386/5-5 (H-GB) ecoTEC plus 637
6 = VUW 196/5-5 (H-GB) ecoTEC plus 825
10 = VUW 246/5-5 (H-GB) ecoTEC plus 832, VUW
246/5-5 (P-GB) ecoTEC plus 832
62 = VUW 306/5-5 (H-GB) ecoTEC plus 835
17 = VUW 286/5-5 (H-GB) ecoTEC plus 838, VUI 286/5-
5 (H-GB) ecoTEC plus 938
Not ad-
justable
D.077 DHW partial load Adjustable cylinder charging output in kW
D.078 DHW max. flow temperature Limit on cylinder charging temperature in °C
50 °C 80 °C
Note
The chosen value must be at least 15 K or 15 °C above
the target cylinder value.
75 °C
D.080 Heating operating hours In hours (h) Not ad-
justable
D.081 DHW operating hours In hours (h) Not ad-
justable
D.082 Heating burner starts Number of burner start-ups Not ad-
justable

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vaillant ecoTEC plus VUW 6/5-5 Series and is the answer not in the manual?

Vaillant ecoTEC plus VUW 6/5-5 Series Specifications

General IconGeneral
BrandVaillant
ModelecoTEC plus VUW 6/5-5 Series
CategoryBoiler
LanguageEnglish

Related product manuals