16
Model Ref.
LE110
Cylinder
1 2 1 2 1 2 1 2 1 2 1 2
Nominal Output Kg/hr 55 55 55 55 55 55 55 55 55 55 55 55
Nominal Output lb/hr 121 121 121 121 121 121 121 121 121 121 121 121
Voltage V 200 200 230 230 380 380 400 400 415 415 440 440
Power input rating Kw N.A. N.A. N.A. N.A. 41.37 41.37 40.91 40.91 41.07 41.07 41.37 41.37
Electrical Supply Ph's N.A. N.A. N.A. N.A. 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph
No. of electrodes
N.A. N.A. N.A. N.A. 6 6 6 6 6 6 6 6
Full load Current A N.A. N.A. N.A. N.A. 66 66 62 62 60 60 57 57
Maximum overcurrent A N.A. N.A. N.A. N.A. 72.6 72.6 68.2 68.2 66 66 62.7 62.7
Fuse Rating/phase A N.A. N.A. N.A. N.A. 80 80 80 80 80 80 80 80
Supply cable terminals mm
2
N.A. N.A. N.A. N.A. 35 35 35 35 35 35 35 35
Unit Total F.L.C. A N.A. N.A. N.A. N.A. 132 124 120 114
Wiring diagram A4-LZD-
560 560 562 560 562 560 562 560 562
Cabinet size
4