EasyManua.ls Logo

Vector TCI-C Series - Temperature Input Configuration

Vector TCI-C Series
21 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
TCI-C-Universal Controller
Doc: 70-00-0123, Date: 20091020 © Vector Controls GmbH Page 18
Universal Input configuration
Parameter Description Range Default
1u 00
Input signal type:
0 = input not active
1 = Analog input: 0…10V or 0…20mA
2 = Analog input: 2…10V or 4…20mA
3 = Passive temperature NTC – Tn10
0 - 3 3
1u 01
Signal display minimum value
-50…205 0
1u 02
Signal display maximum value
-50…205 100
1u 03
Range of universal inputs (For analog inputs only)
0 = x1
1 = x10
2 = x100
0 – 2 0
1u 04
Unit of universal input (For analog inputs only):
0 = no unit
1 = %
2 = °C /°F
3 = Pa
0 – 3 0
1u 05 Samples taken for averaging control signal
0…100 10
1u 06 Calibration Range dep 0
1u 07 Alarm 1: Enable
alarm for lower limit
OFF = Disabled
ON = Enabled
OFF, ON OFF
1u 08 Alarm 1 low limit -40…215 °C 5°C (40°F)
1u 09 Alarm 2: Enable alarm for upper limit
OFF = Disabled
ON = Enabled
OFF, ON OFF
1u 10 Alarm 2 high limit -40…215 °C 50°C (122°F)
1u 11 Alarm 1 and 2 Hysteresis for alarm setbac
k
0…100 ° 5°C (10°F)
Temperature Input configuration
Parameter Description Range Default
1t 00
Temperature input enabled
ON, OFF OFF
1t 01
Signal display minimum value
-50…205 -50
1t 02
Signal display maximum value
-50…205 200
1t 03 Samples taken for averaging control signal
0…100 10
1t 04 Calibration -10.0…10.0 0
1t 05 Alarm 7: Alarm for lower limit of temperature input of LP1
OFF = Not active
ON = Active
OFF, ON OFF
1t 06 Alarm 7 low limit of temperature input
-40…215 °C 5°C (40°F)
1t 07 Alarm 8: Alarm for upper limit of temperature input of LP1
OFF = Not active
ON = Active
OFF, ON OFF
1t 08 Alarm 8 high limit of temperature input
-40…215 °C 50°C (122°F)
1t 09 Alarm 8 Hysteresis for alarm setback
0…100 ° 5°C (10°F)

Related product manuals