Doc: 70-00-0792B V1.3, 20220830  © Vector Controls GmbH, Switzerland   Page 12-34 
Subject to change without notice   www.vectorcontrols.com 
4.2  Selection of actuators and sensors 
Temperature sensors: 
Use Vector Controls NTC sensors to achieve maximum accuracy, see ordering list in chapter 1.3, page 3. 
Binary auxiliary devices (e.g. fans, on/off valves, etc.): 
Do not directly connect devices that exceed specified limits in technical specifications – observe startup current on 
inductive loads. 
4.3  Electrical connection of external inputs 
Use only twisted pair copper conductors for input connections. The operating voltage must comply with the requirements 
for safety extra-low voltage (SELV) as per EN 60 730. 
4.4  Power Failure 
All temperature set points and parameters are automatically saved and do not need to be re-entered. 
4.5  Modbus wiring (TRA-F121-A only) 
4.5.1  Wire type 
An EIA-485 network shall use shielded, twisted-pair cable for data signaling with characteristic impedance between 100 
and 130Ω s. Distributed capacitance between conductors shall be less than 100 pF per meter (30 pF per foot). Distributed 
capacitance between conductors and shield shall be less than 200 pF per meter (60 pF per foot). Foil or braided shields 
are acceptable. 
4.5.2  Line termination 
On last node on either end of the bus connect a 120Ω termination resistor between (+) and (-). 
4.5.3  Maximum length 
The maximum recommended length per segment is 1200 meters (4000 feet) with AWG 18 (0.82 mm2) conductor area 
cable. 
4.5.4  Shield connection 
See Ashrae Standard 135 for detailed recommendation regarding how to connect the shield depending on type of nodes 
present in the network. 
4.5.5  Communication wiring