Comfort temperature set point 
Multiplier: 10 
10.0…40.0 °C (50.0…104.0 °F) 
Economy temperature set point in Heating 
mode 
Heating temperature set point < Cooling 
temperature set point 
Multiplier: 10 
10.0…25.0 °C 
Economy temperature set point in Cooling 
mode 
Cooling temperature set point > Heating set 
point 
Multiplier: 10 
20.0…40.0 °C 
Overheat protection temperature point 
Multiplier: 10; Integer (signed) 
25.0…45.0 °C 
-0.1 = OFF 
Frost protection temperature point 
Multiplier: 10; Integer (signed) 
0.0…16.0 °C 
-0.1 = OFF 
Minimum temperature set point limit in 
heating mode 
Multiplier: 10 
10.0…40.0 °C 
Maximum temperature set point limit in 
heating mode 
Multiplier: 10 
10.0…40.0 °C 
Minimum temperature set point limit in 
cooling mode 
Multiplier: 10 
10.0…40.0 °C 
Maximum temperature set point limit in 
cooling mode 
Multiplier: 10 
10.0…40.0 °C 
 
5.7.2  Temperature set point types 
There are several temperature set points with different functionalities. 
The default temperature set point is the Comfort set point P300. This set point may be directly changed by the user on 
the user interface. It is active during Comfort Mode. 
In Economy mode the economy temperature set point is active (economy heating set point P301 in heating mode and 
economy cooling set point P302 in cooling mode). 
For protection of the facility, overheat protection temperature set point P303 and frost protection temperature set point 
P304 can be defined. In default settings, overheat protection is disabled. 
 
Note 1: If enabled, frost protection and overheat protection are only active in Protection mode. 
Note 2: Comfort set point is not compared with economy heating/cooling set point, nor with frost/overheat protection set 
points. Economy set points are not compared with frost/overheat protection set points. 
 
   
W  Comfort set point 
W
EcoH
  Economy set point heating  
W
EcoC
  Economy set point cooling 
W
Frost
  Frost protection 
W
Overh
  Overheat protection