5.6  System and output configuration 
5.6.1  Parameter P2xx overview 
With parameter P200 – P203 the installed application and valve type can be selected. 
With parameter P204 – P206 the valve characteristics can be set. 
With parameter P207 – P214 the fan configuration can be set. 
 
Application mode: 
2-pipe system: 0…3 
4-pipe system: 4…6 
0 = Heating only 
1 = Cooling only 
2 = 2-pipe manual heating or cooling 
3 = 2-pipe auto heat/cool changeover 
4 = 4-pipe manual heating or cooling 
5 = 4-pipe auto heat/cool changeover 
6 = 4-pipe Heating and cooling 
7 = Floor heating system 
8 = Chilled ceiling system 
9 = Heated/chilled ceiling system 
0 = OFF = Electric heater disabled 
1 = ON = Electric heater enabled 
Fan extension time after electric 
heating 
Valve type of heating/cooling system 
0 = on/off valve 
1 = 3-position valve (only for 2-pipe systems) 
3-position valve running time 
Minimum on time of valve for on/off 
type 
Minimum off time of valve for on/off 
type 
1 = 1 fan speed (only DO1) 
3 = 3 fan speeds 
Minimum on time of each fan speed 
Low fan speed switch on level 
(Switch off level 15% lower or 0%) 
Note: Ignored for on/off valve (and 
electric heater), see chapter 5.8 
Control settings 
Medium fan speed switching point 
(Switch off level 15% lower) 
High fan speed switching point 
(Switch off level 15% lower) 
0 = OFF = Fan kick disabled 
5…1500 = period in minutes 
Minimum fan speed in auto mode 
0 = Fan off 
1 = Low speed 
Minimum fan speed in manual mode 
0 = Fan off 
1 = Low speed