5.8.7  Fan control in automatic mode (on/off control)  
 
Note: 
•  Fan is off only if the valve (or electric heater) is turned off. 
•  This chart shows the fan control for 2-pipe and 4-pipe heating or cooling applications (P200 = 0 to 5). 
For 4-pipe heating and cooling application (P200 = 6), the dead zone between heating and cooling switch point is 
not depicted. 
•  This chart assumes P213 (Minimum fan speed in auto mode) is set to 0 = Fan off (default). 
 
Fan speed 1 is aligned with on/off valve (or electric heater). If the valve (or electric heater) switches ON for 
heating/cooling then the fan speed 1 is switched ON. If the valve (or electric heater) switches OFF then the fan speed is 
switched OFF (in case P213 minimum fan speed in auto mode is 0)