Press up and down for minimum 3 seconds to enter the password protected default settings. 
Enter the default settings with CODE 245. Choose between default TRA-F12x-A “dEF” and OEM “OE” configuration copy 
menu. Navigate with Up ( ), Down ( ), Enter ( ) and Return Buttons ( ,  ). 
After a load or store action the small digits show “Good” and the default settings menu is closed. 
 
Action with Enter Button ( ) 
No action 
Load default TRA-F12x-A configuration (as described in this manual) 
No action 
Load default OEM configuration 
Save default OEM configuration 
 
5.10.2  With Modbus 
Via Modbus the default settings can be accessed by writing 2 registers (with function code 0x16 write multiple registers) 
to data address 37. After a load or store command via Modbus, the small digits show “Good” and the large digits show 
“CPy” on the user interface. 
 
Default configuration type 
2 registers 
(function code 
0x16: write multiple 
registers) 
0 = Default TRA-F12x-A configuration 
1 = OEM default configuration 
Action for default configuration 
0 = No action 
1 = Load config. as defined with address 37 
2 = Save actual config. to OEM default 
(only valid when address 37 = 1)