5.6.7  Periodic fan kick 
The periodic fan kick is disabled by default settings. 
In automatic fan mode, if the fan speed is 0, the fan will be set to fan speed 1 periodically with the time defined with 
P212. The fan runs after this period for the minimum on time for fan speeds (P208). 
 
5.6.8  Floor heating system with or without floor temperature limitation 
Detailed explanation of floor temperature limitation is given in chapter 5.9 Temperature and digital inputs, page 27. 
The floor heating system can be configured with or without floor temperature limitation. 
 
with floor temperature limitation 
without floor temperature limitation 
P500/P502 (Input RT1/RT2 
Configuration) 
2 = Heat/cool changeover or floor 
temperature sensor (NTC or DI) 
P501/P503 (Definition of RT1/ RT2) 
0 = NTC temperature sensor 
P505 (Floor temperature limit) 
Set limitation (Default: 30°C/86°F)