4 Mounting
4.1 General instructions
Make sure that all parts of the instrument exposed to the process, in
particular the sensor element, process seal and process tting, are
suitable for the existing process conditions. These include above all
the process pressure, process temperature as well as the chemical
properties of the medium.
You can nd the specications in chapter "Technical data" or on the
type label.
Select an installation position you can easily reach for mounting and
connecting as well as later retrotting of an indicating and adjustment
module. The housing can be rotated by 330° without the use of any
tools. You can also install the indicating and adjustment module in four
dierent positions (each displaced by 90°).
Before beginning the welding work, remove the electronics module
from the sensor. By doing this, you avoid damage to the electronics
through inductive coupling.
With threaded versions, the housing must not be used to screw in the
instrument! Applying tightening forces on the housing can damage its
internal parts.
Use the hexagon for screwing in.
Use the recommended cables (see chapter "Connecting to power
supply") and tighten the cable gland.
You can give your instrument additional protection against moisture
penetration by leading the connection cable downward in front of the
cable entry. Rain and condensation water can thus drain o. This
applies mainly to outdoor mounting as well as installation in areas
where high humidity is expected (e.g. through cleaning processes) or
on cooled or heated vessels.
Suitability for the pro-
cess conditions
Mounting position
Welding work
Handling
Moisture
10 VEGAFLEX 61 Probus PA
4 Mounting
31835-EN-100426