5 Set up the sensor with the display and adjustment module
VEGAFLEX 86 • Modbus and Levelmaster protocol
47614-EN-230605
signal suppression to achieve the best possible accuracy. This should
be done with the lowest possible level so that all potential interfering
reectionscanbedetected.
Enter the actual distance from the sensor to the medium surface.
All interfering signals in this section are detected by the sensor and
stored.
The instrument carries out an automatic false signal suppression
as soon as the probe is uncovered. The false signal suppression is
always updated.