EasyManua.ls Logo

Vega VEGAMET 861 - Page 45

Vega VEGAMET 861
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
45
11 Applications and functions
VEGAMET 861 • 4 … 20 mA/HART
58866-EN-200401
Via the digital inputs, possible fault signals of the pumps can also be
evaluated.Youcanndthedescriptionofthisintheapplicationexam-
ple "Pump control 1/2" under "Pump monitoring".
Thispumpcontrolsystemoerstwodierentoptions:
Pump control 3: The upper switching point determines the switch-
opointfortherelay,whereasthelowerswitchingpointdeter-
mines the switch-on point
Pump control 4: The upper switching point determines the switch-
on point for the relay, whereas the lower switching point deter-
minestheswitch-opoint
The sequence cannot be changed, the relay with the lowest index is
switchedonrst,thentherelaywiththenexthigherindex.Afterthe
relay with the highest index, the relay with the lowest index follows, for
example Rel. 1 -> Rel. 2 -> Rel. 3 -> Rel. 4 -> Rel. 1 -> Rel. 2 …
The sequence applies only to those relays assigned to the pump
control.
In a waste water disposal system, a sump should be pumped empty
when a certain level is reached. Three pumps are available for this. At
60 % level, pump 1 should run until the level has fallen below 10 %.
If the 60 % point is exceeded again, the same task is transferred to
pump 2. In the third cycle, pump 3 is activated; after that, pump 1
again. If the level continues to rise despite operation of a pump, an
additional pump switched on when the level exceeds the 75 % switch-
ingpoint.Andifthelevelstillrisesfurtherduetoextremeinowand
exceeds the 90 % limit, pump 3 is also switched on.
For relay 1 … 3, the mode of operation "Pump control 4" is adjusted
with the option "Sequenced operation". The relay switching points are
conguredasfollows:
Select in the DTM navigation section the menu items "Meas. loop -
Outputs - Relay".
Relay 1 upper switching point = 60.0 %
Relay 1 lower switching point = 10.0 %
Relay 2 upper switching point = 75.0 %
Relay 2 lower switching point = 10.0 %
Relay 3 upper switching point = 90.0 %
Relay 3 lower switching point = 10.0 %
The function of pump control 4 is shown in detail in the following dia-
gram. The previously described example is used as a basis.
Example

Table of Contents

Other manuals for Vega VEGAMET 861

Related product manuals