52
12 Diagnostics and servicing
VEGAMET 861 • 4 … 20 mA/HART
58866-EN-200401
incorrect parameter adjustment, a fault signal is triggered. In case of
an instrument defect or line break/shortcircuit, a fault signal is also
triggered.
The fault indication lights up in case of failure and the current output
aswellastherelaysreactaccordingtotheconguredfaultmode.If
thefailsaferelaywascongured,itwilldeenergize.Inaddition,one
of the following error messages is outputted on the display and the
background lighting changes to colour acc. to NAMUR NE 107.
Error code Cause Rectication
F002
Measuring point
notcongured
Measuring point
was not yet con-
gured
No sensor assigned.
For measuring point 3: No application
with 3 measuring points was selected.
F003
Hardware: CRC
error
CRC error (error
with self-check)
Switchtheinstrumento/on
Carry out a reset
Send instrument for repair
F008
Sensor input:
Failure, sensor
Sensor not found Check connection of the sensor
Check HART address of the sensor
F012
Hardware: AD
converter
Hardware error,
sensor input
Switchtheinstrumentoandon
Send instrument for repair
F013
Sensor input:
Sensor error
The input of the
measuring point
returns an error
The connected
sensor returns
an error
Switchdevice/sensoroanon
Send device/sensor for repair
F014
Sensor input:
Short-circuit
Sensor cur-
rent > 21 mA or
short-circuit
Check sensor, e.g. on failure
Remove short-circuit
F015
Sensor input:
Line break
Sensor in boot
phase
Sensor current
< 3.6 mA or line
break
Check sensor, e.g. on failure
Remove line break
Check connection of the sensor
F034
EEPROM: CRC
error
EEPROM: CRC
error
Switchtheinstrumentoandon
Carry out a reset
Send instrument for repair
F035
ROM defective
ROM: CRC error Switchtheinstrumentoandon
Carry out a reset
Send instrument for repair
F036
RAM
RAM error Switchtheinstrumentoandon
Carry out a reset
Send instrument for repair
F037
RAM
RAM defective Switchtheinstrumentoandon
Carry out a reset
Send instrument for repair
Failure