VEGAMET 861 • 4 … 20 mA/HART
58866-EN-200401
Temperature error relating to 20 mA 0.008 %/K
Adjustment range HART sensor ± 10 % of sensor measuring range
Connection cable to the HART sensor two-wire screened standard cable
Digital input
Quantity 2 x digital input
Input type active
Ʋ Voltage > 14 V DC
Ʋ Current > 3 mA
Ʋ Max. load 200Ω
Input type passive
Ʋ Switching threshold Low -3 … 5 V DC
Ʋ Switching threshold High 11 … 30 V DC
Ʋ Max. input voltage 30 V DC
Ʋ Max. input current 30 mA
Ʋ Max. sampling rate 10 Hz
Ʋ Input impedance 8kΩ
Relay output
Quantity 4xoperatingrelay,onecanbeconguredasfailsafe
relay
Function Switching relay for level, fault signal or pulse relay for
ow/samplingpulse,pumpcontrol
Contact Floating spdt
Contact material AgSnO2, hard gold-plated
Switching voltage max. 250 V AC/60 V DC
Switching current max. 1 A AC (cos phi > 0.9), 1 A DC
Breaking capacity
3)
min. 50 mW, max. 250 VA, max. 40 W DC (with
U < 40 V DC)
AC/DC operation Mixed operation with AC/DC voltage is not permitted for
the relay outputs
Min. programmable switching hysteresis 0.1 %
Mode pulse output
Ʋ Pulse length 350 ms
Current output
Quantity 1 x output
Function Level/ow/samplingpulse
Range 0/4 … 20 mA, 20 … 0/4 mA
Resolution 1 µA
Max. load 500Ω
3)
If inductive loads or stronger currents are switched through, the gold plating on the relay contact surface will be
permanently damaged. The contact is then no longer suitable for switching low-level signal circuits.