5 Connecting to the bus system
VEGAPULS 68 • Foundation Fieldbus
36538-EN-170405
5.7 Wiring plan - version IP 66/IP 68, 1 bar
1
2
Fig. 37: Wire assignment in permanently connected connection cable
1 Brown (+) and blue (-) to power supply or to the processing system
2 Shielding
5.8 Switch-on phase
After VEGAPULS 68 is connected to the bus system, the instrument
carries out a self-test for approx. 30 seconds. The following steps are
carried out:
Internal check of the electronics
Indication of a status message, e.g. "F 105 Determine measured
value" on the display or PC
Statusbytegoesbrieytofaultvalue
Then the actual measured value is outputted to the signal cable. The
value takes into account settings that have already been carried out,
e.g. default setting.
Wire assignment, con-
nection cable