49
6 Set up with the display and adjustment module
VEGAPULS 68 • Foundation Fieldbus
36538-EN-170405
constant. Keep in mind that layer interfaces can cause faulty meas-
urements.
If you want to measure the total height of both liquids reliably, please
contact our service department or use an instrument specially de-
signed for interface measurement.
Through this selection the operating range of the sensor is adapted
to the vessel height, which considerably increases measurement
certaintyunderdierentbasicconditions.
The min. adjustment must be carried out independently of this.
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Apart from the medium and the application, the vessel form itself can
inuencethemeasurement.Toadaptthesensortothesemeasuring
conditions,thismenuitemoersdierentoptionsforvesselbottom
and ceiling for certain applications.
Enter the requested parameters via the appropriate keys, save your
settings with [OK] and jump to the next menu item with the [ESC] and
the [->] key.
Since the radar sensor is a distance measuring instrument, it is the
distance from the sensor to the product surface that is measured. To
indicate the actual level, the measured distance must be assigned to
a certain height percentage.
To perform the adjustment, enter the distance with full and empty ves-
sel, see the following example:
Setup - Vessel height,
measuring r
ange
Setup -
Vessel form
Setup - Adjustment