SI23 Solar Pump VFD Manual
32
F10.18(0x0A12)
Bus
undervoltage
suppression gain
V/F SVC
Set the response effect of undervoltage
suppression.
100.0%
(0.0%500.0%)
F10.19(0x0A13)
Bus
undervoltage
protection point
V/F SVC
The lower limit voltage allowed by the set bus
voltage. Below this value, the VFD reports an
undervoltage fault.
T3: 320
S2: 190
(T3: 300400
S2: 160240)
Also subject to
overvoltage limit
T3
overvoltage
point: 820V
(750840)
S2
overvoltage
point 400V
(360410)
F10.20(0x0A14)
Input and output
phase loss
protection
options
V/F SVC FVC
Set whether the input and output phase loss
protection functions are enabled.
LED "0" digit: Output phase loss protection.
0: Off
1: On
LED "00" digit: Input phase loss protection.
0: Off
1: On, detected the input missing phase report
warning A.ILF, continue to run
2: Turn on, detect input missing phase report
fault E.ILF, free stop
021
(000121)
F10.22(0x0A16)
Ground short
circuit protection
option
V/F SVC FVC
Set whether the VFD output and the VFD
cooling fan ground short circuit protection
function are enabled.
LED "0" digit: Output short circuit protection.
0: Off 1: On
LED "00" digit: Fan to ground short circuit
protection.
0: Off
1: On
11
(0012)
F10.23(0x0A17)
Fan ON/OFF
control selection
Set the VFD cooling fan operation mode.
0: The fan runs after the VFD is powered on.
1: After the shutdown, the fan operation is
related to temperature, and the operation is
running.
2: After the shutdown, the fan stops after
F10.24, and the operation is related to
temperature.
1
(02)