SI23 Solar Pump VFD Manual
33
V/F SVC FVC
Set the number of fault self-recovery that is
allowed to be performed.
Note: A value of 0 indicates that the fault
self-recovery function is turned off; otherwise it
indicates that the function is enabled.
Failure
self-recovery
interval
V/F SVC FVC
Set the waiting time before the VFD resets to
the time before each reset.
Numbers of
failures
recovered
V/F SVC FVC
Indicates the number of self-recovery faults that
have been performed. This parameter is a
read-only parameter.
Range of settings and definition
Factory default
(setting range)
V/F SVC FVC
0: Not locked.
1: Keyboard function parameter modification
lock.
2: Function parameters and non-start stop
button lock.
3: Function parameters and button full lock.
Parameter 1
showed up on
first line of the
keyboard
V/F SVC FVC
LED "0" and "00" digit: Setting yy setting in
monitoring parameter number Cxx.yy
00~63.
LED "000" and "0000" digit: Monitoring
parameter number Cxx.yy xx setting
00~07.
Parameter 2
showed up on
first line of the
keyboard
V/F SVC FVC
LED "0" and "00" digit: Setting yy setting in
monitoring parameter number Cxx.yy
00~63.
LED "000" and "0000" digit: Monitoring
parameter number Cxx.yy xx setting
00~07.
Parameter 3
showed up on
first line of the
V/F SVC FVC
LED "0" and "00" digit: Setting yy setting in
monitoring parameter number Cxx.yy