EasyManuals Logo

Velux KFC 100J User Manual

Velux KFC 100J
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
7 VELUX
®
Indications / Technical data
Further diagnosis / Monitoring in the control unit
LED on the printed circuit
board
Functions Diagnosis
Alarm = Alarm
(red)
ON Fire alarm triggered
Wind-/Regen = Wind/rain
(green)
ON Wind/rain sensor triggered
RESET button: A fire alarm is reset with the RESET button. The motors close the staircase smoke exhaust.
Connection values
Protect mains connection cable separately on site.
1) Input 230 V / 50 Hz (±10 %) 150 VA
2) Output 24 V - 4,8 A
Fuses
3) Mains 1 A slow
4) Motor 5 A slow
5) Battery 630 mA medium slow
Connection options
1. Motor up to 4,8 A.
2. Smoke detector/temperature detector, up to 10 units.
3. Break-glass point, up to 4 units.
4. Secondary break-glass points, up to 15 units.
5. Ventilation switch with OPEN indicator, up to 15 units, or without OPEN indicator, no limitations.
6. Wind/rain sensor with potential-free normally open contact.
7. Alarm activation via a potential-free fire alarm system contact at the smoke detector input (fire alarm module insertion)
8. 24 V / 100 mA on extra terminal. Warning: No 72-hour emergency power supply when in use.
Further technical data
Nominal voltage 24 V
Open circuit voltage at 230 V AC 28 V DC
Motor voltage at 230 V AC 4.8 A - load 22 V DC
Ripple at full load Max 6 % (= 3.5 Vpp)
Emergency power supply for back-up batteries (2 x 12 V / 3.4 Ah) 72 hours in case of power failure
Charging voltage 27.7 V to 27.8 V at 20 C°, charging current is limited to
about 350 mA.
Housing material: Plastic (housing for installation on wall/recessed installation)
Housing for installation on wall is included.
Colour: White (RAL 9016)
Size: 368 mm x 353 mm x 97 mm (W x H x D)
The back of the housing in the wall cut-out
(cut-out dimension): 325 mm x 311 mm x 80 mm (W x H x D)
Weight: 4.7 kg without battery, 7.5 kg with battery
Operating conditions: -5 °C to +40 °C, max 90 % relative humidity (non-condensing).
Protection degree: IP 30
Cable entries from above.
All connection terminals (except the mains terminal)
are insertable.
Terminal size for 2.5 mm²