EasyManua.ls Logo

VENTILATORS VH30100 - Installation; Installation of the HRV;ERV; Insulated Flex from Unit to Outside Wall

VENTILATORS VH30100
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INSTALLATION
WWW.CLEANCOMFORT.COM
8
IO-VENT-SS
Installation of the HRV/ERV
IMPORTANT Minimum installaon requirements:
a) Minimum two 2"x 4" (50.8 mm x 101.6 mm) wood
wall studs and minimum ⅜" (9.5 mm) thick drywall is
required to secure the HRV/ERV wall bracket.
b) Support for weight of 80 lbs, which includes HRV/
ERV, duct connecons and accessories. Proper instal-
laon requires that the unit be secured to the wall. If
there are no wall studs available, secure a sheet of ¾"
plywood to wall then fasten wall mounng bracket
to plywood.
Tip to installer: If the unit is not level, improper
drainage will occur and could lead to moisture and
leakage problems.
It is recommended that approximately 16 inches of exible
duct be installed between the HRV or ERV and your rigid
duct. The exible duct is connected to the HRV or ERV in
the same way as the insulated ex.
Insulated Flex from Unit to Outside Wall
Tip to installer: To ensure a beer installaon and to
avoid an undesired bend in the duct, align the exible duct
with the collar before securing over the four hooks on the
inner surfaces of the collar.
All ducng to and from the HRV/ERV must be adequately
insulated to minimize heat loss and gain. All tapes,
mascs, and nonmetallic clamps used for eld installaon
of exible ducts shall be listed and labeled to Standard UL
181B - Closure Systems for Use With Flexible Air Ducts and
Air Connectors.
Once insulated ex is aached to the collar, slide collar into
the keeper secon and aach collar to the unit with four,
#10 x 5/8" screws supplied in installaon kit to ensure a
proper seal. See Figures 9-13 on following page.
Figure
5
Installaon of the wall bracket. Secure with two
#10 x 1
1
⁄4" screws.
Figure 6 Hang HRV/ERV on
the wall-mounng bracket.
Figure 7 Before compleng
the installaon, make sure
that the HRV/ERV is level.
Figure 8 Secure HRV/ERV to
wall-mounng bracket with
the two, #8 x 38" screws.
NOTE: Clean Comfort Venlators (HRV/ERV) that use a
fan shut down defrost sequence for frost protecon are
NOT equipped with a motorized outdoor air damper.
Special consideraon is required when one of the follow-
ing types of installaons is chosen:
a) Exhaust at the source and supply in the return air duct,
or
b) Exhaust and supply in the return air duct
The HRV/ERV must operate in the connuous venlaon
mode to avoid cold, uncondioned air being introduced
through the unit and directly into the furnace during
heang season. However if the homeowner chooses to
run the unit in Intermient (“INTER”) mode or turn it
“OFF”, cold supply air will be drawn in through the HRV/
ERV when the system’s blower fan is operang e.g. during
a heang cycle. We recommend installing a motorized
damper between the HRV/ERV supply air connecon
and the furnace’s return air duct that will automacally
close when the HRV/ERV is not operang. You may also
consider the installaon of a backdra damper on the
venlators exhaust air connecon to prevent cold air
inltraon.
Alternavely, installing a venlator that employs a
recirculang defrost sequence and is equipped with
an integrated motorized outdoor air damper, such as
the VH30120R or VH30160R, would avoid the problem
described above.