20
PU SENS 01
www.ventilation-system.com
FACTORY SETTINGS
PARAMETER DEFAULT SETTINGS
MEASUREMENT
UNIT
Air flow rate 1 -
Temperature
Duct 25
°С
Room 20
Air flow setting
Air supply
first speed 40 %
second speed 70 %
third speed 99 %
%
Air extract
first speed 40 %
second speed 70 %
third speed 99 %
Temperature sensor Duct -
Language selection English -
Extra options
Heating control OFF ON/OFF
Supply fan off mode OFF ON/OFF
Humidity sensor selection 2 -
Bypass operation mode 1 -
Supply fan off mode
Working hours 20 Minute
Downtime 5 Minute
Switch-off temperature -1 °С
Standby mode setting
Air flow rate 0 -
Temperature 20 °С
Display brightness adjustment
Operation 50 -
Sleep 1 -
Humidity setting
Duct 50 %
Room 50 %
Temperature sensor correction -4 °С
Timer settings
Hours 01 Hour
Minutes 00 Minute
Air flow rate 1 -
Temperature 20 °С
Motor hours Air handling unit 3000 Hour
ERROR CODE DESCRIPTION
ERROR
CODE
HEATER TYPE
ELECTRIC WATER
TE1 Outdoor temperature sensor malfunction.
TE2 Malfunction of the heat exchanger freezing protection sensor.
TE3 Return heat medium temperature sensor malfunction.
TE4 Water heater freeze protection sensor malfunction.
TE5 Duct temperature sensor malfunction.
MIN Supply fan malfunction.
MEX Exhaust fan malfunction.
ERP Control panel communication error.
DI1 TK60 overheating sensor activation.
DI2 Fire alarm sensor actuation.
DI3 TK90 overheating sensor activation.
DI5 Water pressure sensor malfunction.