60 Chapter 8 Options
APM 300 Integrated UPS Single Module And Parallel System User Manual
Chapter 8 Options
This chapter provides the UPS option list, and introduces the functions, installation and configuration of each
option.
8.1 Option List
Table 8-1 lists all of the UPS options.
Table 8-1 Option list
1
inductor
UF-NRBYPCK 02355086 Applicable to APM 300 UPS
2
sensor
UF-SENSOR 02350174
4 Relay card UF-DRY410 02354309
Installed in Intellislot 1 or 3 port,
advisably in Intellislot 3 port
5 SIC card UF-SNMP810 02351817
Installed in Intellislot 1, 2 or 3
port, advisably in Intellislot 2 port
6 UF-RS485 card UF-RS485 02351786
Installed in Intellislot 1 or 3 port,
advisably in Intellislot 3 port
7 Modbus card UFMOD41Z1 02354066
Installed in Intellislot 1 or 3 port,
advisably in Intellislot 3 port
8
LBS cable (5m, 10m,
15m)
10m cable (04118684)
15m cable (04118685)
Two cables should be selected to
achieve redundancy
9
Parallel control cable
(5m, 10m, 15m)
10m cable (04118684)
15m cable (04118685)
Two cables should be selected to
achieve redundancy
8.2 Option
8.2.1 Bypass Load Sharing Inductor
Install the bypass load sharing inductors for the parallel system comprised of two or more UPS modules, to
ensure the bypass output load sharing for the parallel system. The bypass load sharing inductor is used to
compensate the impedance differentia between SCR and cable.
Each UPS cabinet has three bypass load sharing inductors, with no extra clearance occupied. The load sharing
rate is generally 10% of the system rated current with the difference of external cable configuration. Try to
make the cable length be the same from bypass to each UPS and from UPS module output to parallel system
connection point.
Preparing installation tools
Make sure that all installation tools are present, including a cross head screwdriver, a pair of diagonal cutting
pliers, a sleeve spanner and an adjustable spanner.