Chapter 11 Specifications 73
APM 300 Integrated UPS Single Module And Parallel System User Manual
Chapter 11 Specifications
The chapter provides the UPS specifications.
11.1 Conformity And Standards
The UPS has been designed to conform to the European and international standards listed in Table 11-1.
Table 11-1 European and international standards
General and safety requirements for UPS
EN62040-1/IEC62040-1/AS62040-1
EN50091-2/IEC62040-2/AS 62040-2 (C3)
Method of specifying the performance and test
requirements of UPS
EN50091-3/IEC62040-3/AS 62040-3 (VFI SS 111)
The product standards in this table incorporate relevant compliance clauses with generic IEC and EN standards for safety
(IEC/EN/AS60950), electromagnetic emission and immunity (IEC/EN/AS61000 series) and construction (IEC/EN/AS60146
series and 60529).
11.2 Environmental Characteristics
Table 11-2 Environmental characteristics
Noise within 1m (in the front) dB 56 58 60
Altitude m
≤
1000, derate power by 1% per 100m between 1000m and
2000m
0
~
40; battery life is halved for every 10
°
C increase above 20
°
C
Storage and transport temperature
for UPS
°
C -25
~
+55
Recommended battery storage
temperature
°
C -20
~
+30 (20
°
C for optimum battery storage)
11.3 Mechanical Characteristics
Table 11-3 Mechanical characteristics
Protection degree, IEC (60529)
IP20 (front door open or closed, back door closed)