Appendix
Vertiv | Liebert CRD10 | User Manual 110
Supply Avg Temp SP, Default 23C (73.4F), Range 15 to 32C (59 to 89.6F)
Return Avg Temp SP, Default 32C (89.6F), Range 18 to 40C (64.4 to 104F)
Remote Avg Temp SP, Default 23C (73.4F), Range 15 to 32C (59 to 89.6F)
Supply Avg Hum SP, Default 50%, Range 20% to 60%
Sup High Temp Alarm SP, Default 27C (80.6F), Range 20 to 35C (68 to
95F)
Sup Low Temp Alarm SP, Default 8C (46.4F), Range 5 to 20C (41 to 68F)
Rtn High Temp Alarm SP, Default 40C (104F), Range 30 to 45C (86 to
113F)
Rtn Low Temp Alarm SP, Default 18C (64.4F), Range 5 to 25C (41 to 77F)
Rtn High Hum Alarm SP, Default 60%, Range 50% to 99%