Mechanical Installation
Vertiv | Liebert CRD10 | User Manual 30
3.3.2
Top plate pipe outlet Locations & Dimensions
The locations of the pipe inlets and outlets on the unit top plate are shown in Figure 3-4 and corresponding
dimensions of the top plate pipe outlet are tabulated in Table 3-4.
Figure 3-4 Top Plate Locations for Pipe Outlets
Table 3-4 Dimension of Top Plate Pipe Outlet (mm/inch)
UNIT TOP CONNECTIONS
CRD10
RLT
Refrigerant Liquid Line Inlet
1/2" O.D. Copper Sweat
RGT
Refrigerant Gas Line Outlet
5/8" O.D. Copper Sweat
CPT
Condensate Pump
NPT 1/2" (Rc1/2”) Female copper threaded joint
HVT
High Voltage Top Connection
Combination Knockout
1-1/8" (29 mm)
LVT
Low Voltage Top Connection
Knockout Hole Diameter
7/8" (22 mm)
NOTE: NPT threaded joint is for UL model, Rc threaded joint is for CE model.