How to troubleshoot a Vertiv Liebert PEX EC fan that won't start?
- JJonathan PierceAug 5, 2025
If the Vertiv Air Conditioner's EC fan won't start, the issue might stem from a disconnected power supply. Start by verifying the MCB of the main fan. Then, check if the L1, L2, and L3 fan power lines are off, experiencing a phase failure, or suffering from undervoltage. Alternatively, a control panel failure could be the culprit. Check for a 24 Vac voltage between points P36-3 and E1; if absent, inspect the control panel. Also, check the green LED next to silicon control Q5 on the control panel to see if it's illuminated. Finally, a voltage issue might exist. Check if the voltage between P53-2 and P53-3 is less than 10 Vdc; if not, examine the control panel.