Vertiv | Liebert PEX+Chilled Water | User Manual 66
iCOM Controller Operation
Figure 4-9 Networking of the Multiple Units
4.10. Teamwork Modes
Following are the teamwork modes to group Liebert PEX+CW units in a network
No Teamwork
Teamwork Mode 1
Teamwork Mode 2
Teamwork Mode 3
All Liebert iCOM controlled cooling units in a network must be set to run in the same teamwork mode
4.10.1. Application of Teamwork Modes
No Teamwork: Multiple zones in one room
All cooling units work independently, responding to their own sensors. Standby function and unit rotation are
possible, but cascading is not possible (refer Section 4.10.3 Standby and Cascade). Auto set will not adjust the
proportional band in this mode.