Vertiv | Liebert® GXT5 | Installer/User Guide 17
Chapter 2: Installation
Do not start the UPS until after the installation is finished, the system is commissioned by an authorized engineer,
and the external-input circuit breakers are closed�
WARNING! Risk of electric shock
Can cause equipment damage, injury and death. Before beginning installation, verify that all external overcurrent
protection devices are open (O), and that they are locked-out and tagged appropriately to prevent activation
during the installation, verify with a voltmeter that power is O and wear appropriate, OSHA-approved
personal protective equipment (PPE) per NFPA 70E. Failure to comply can cause serious injury or death. Before
proceeding with installation, read all instructions. Follow all local codes
.
2.1. Unpacking and Inspection
Unpack the UPS and conduct the following checks:
Inspect the UPS for shipping damage� If any shipping damage is found, report it to the carrier and your local
Vertiv representative immediately
Check the accessories included against the packing list� If there is any discrepancy, contact your local Vertiv
representative immediately
CAUTION
The UPS is heavy (see Specifications on page 57, for the weight). Take proper precautions when lifting or
moving the unit.
2.2. Pre-installation Preparation
Install the UPS indoors in a controlled environment, where it cannot be accidentally turned O� The installation
environment should meet the specifications listed in Specifications on page 57
Place the UPS in an area of unrestricted air-flow around the unit, away from water, flammable liquids, gases,
corrosives, and conductive contaminants� Avoid direct sunlight
NOTE: Operating the UPS in temperatures above 77°F (25°C) reduces battery life.
2.2.1. Installation Clearances
Maintain at least 4 in� (100 mm) clearance in the front and rear of the UPS� Do not obstruct the air inlets on the
front panel and rear panel of the UPS� Blocking the air inlets reduces ventilation and heat dissipation, shortening
the service life of the unit�

Table of Contents

Other manuals for Vertiv Liebert GXT5-2000LVRT2UXL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vertiv Liebert GXT5-2000LVRT2UXL and is the answer not in the manual?

Vertiv Liebert GXT5-2000LVRT2UXL Specifications

General IconGeneral
BrandVertiv
ModelLiebert GXT5-2000LVRT2UXL
CategoryUPS
LanguageEnglish

Related product manuals